Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T13CM06036
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/06/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The specified backflow prevention device, Watts 9BD, is not listed for ASSE 1022 as required for coffee machines and non-carbonated beverage dispensers. Reference: Section 608.16.10, IPC 2012. 2. Verify that the proposed backflow preventers will be accessible for inspection, maintenance and, if they have a relief port, the port shall discharge to a point where water leakage will not cause damage. Reference: Sections 608.14 and 608.15.1, IPC 2012. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/19/2013 | CPIERCE1 | REJECT SHELF | Completed |