Review Date Reviewer's Name Type of Review Description Status Comments
11/06/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The specified backflow prevention device, Watts 9BD, is not listed for ASSE 1022 as required for coffee machines and non-carbonated beverage dispensers. Reference: Section 608.16.10, IPC 2012.
2. Verify that the proposed backflow preventers will be accessible for inspection, maintenance and, if they have a relief port, the port shall discharge to a point where water leakage will not cause damage. Reference: Sections 608.14 and 608.15.1, IPC 2012.