Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T13CM05957
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/04/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 11/12/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/18/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 11/25/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The waste and vent diagram shows 4" pipes served by 3" cleanouts. Provide cleanouts sized for the nominal size of pipes that they serve. Reference: Section 708.7, IPC 2012. [Initial comment: Provide plumbing plans for the new work, including water isometrics and waste and vent isometrics. Reference: Section 107.2.1, IBC 2012.] 2. The specified temperature mixing valve (Leonard model TA-F) is listed to ASSE 1016, not ASSE 1070 and is not acceptable. [Initial comment: Provide tempered water for the lavatories using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.] 3. Install the proposed vacuum relief valve for the water heaters per the manufacturer's listing information, i.e. with no valves located between the vacuum relief valve and the water heater. Reference: Section 303.2, IPC 2012. [Initial comment: Provide a detail of the water heater installation, including the excess pressure relief, expansion tank, vacuum relief or other anti-siphon device, safety pan, and valves. "Reference only" details are not acceptable. Reference: Sections 502.1, 503.1, 503.2, 504, 606.1, and 607.3 IPC 2012.] 4. Section 1003.3, IPC 2012, as amended by the City of Tucson, has a specific calculation method for determining the required minimum size for a gravity grease interceptor. Table 1003.3.4.1, IPC 2012 applies to hydromechanical and automatic grease interceptors, not gravity grease interceptors. [Initial comment: Provide sizing calculations for the gravity grease interceptor. Verify that the 500-gallon gravity grease interceptor is adequate for the proposed load. Reference: Section 1003.3, IPC 2012, as amended by the City of Tucson.] |
| 11/25/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | The ventilation calculations show that the outside air flow meets the requirements of Section 403.3, IMC 2012 but the exhaust airflow rate for the backbar area does not comply with Sections 403.3 and 507.2.2, IMC 2012. [Initial comment: Provide calculations demonstrating adequate ventilation using the current code (2012 IMC). Reference: Section 403.2, IMC 2012.] |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/12/2013 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |
| 12/12/2013 | CPIERCE1 | REJECT SHELF | Completed |