Permit Number: T13CM05900
Parcel: 105110700

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM05900
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/25/2013 STEVE SHIELDS ZONING REVIEW Approved
09/25/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Needs Review
09/25/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review
09/25/2013 ROBERT SHERRY WATER REVIEW Approved
09/25/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET T2.1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE SPECIFICATIONS.
2. SHEET A1.1 (FLOOR PLAN); KEYNOTES: NOTE 15 INDICATES A BOTTLE FILLING STATION (IN LIEU OF A HIGH/LOW DRINKING FOUNTAIN OR A SINGLE POINT OF USE WATER DISPENSER). A CONTAINER FOR THE WATER MUST BE PROVIDED TO THE PATRONS, AND THE HEIGHT OF THE ACTUAL DISPENSER MUST MEET THE ACCESSIBLE HEIGHT AS INDICATED IN THE ICC/ANSI A117.1, FIGURE 602.5. VERIFY AND PROVIDE.
3. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
09/25/2013 JASON GREEN ENGINEERING REVIEW Approved
09/25/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Needs Review
09/25/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
09/26/2013 CPIERCE1 WWM REVIEW Completed
09/26/2013 KEN BROUILLETTE FIRE REVIEW Approved