Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T13CM05881
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/30/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
11/01/2013 | STEVE SHIELDS | ZONING | REVIEW | Denied | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: A-Family Discount Storage - 8950 E. Speedway Blvd. T13CM05881, T13CM05883, T13CM05884, T13CM05886, & T13CM05886 Building Plan (2nd Review) TRANSMITTAL DATE: November 1, 2013 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Sheet SG-1, Drawing Index does not match the order if the drawings. 3. This comment was not addressed. There are still LUC references on sheet SG-2, i.e. floor area ratio, development designators etc. Remove all references from the plan. Sheet SG-2 references the Land Use Code (LUC). As the LUC is not longer applicable and the development package was reviewed under the Unified Development Code (UDC) remove all references to the LUC from this sheet or remove the sheet. 4. Zoning has reviewed the floor plans and elevations for Buildings 16, 17, 18,19 & 20 and they appear to reflect what is proposed for the DP. 5. Once the above comments are addressed and all other PDSD agencies have approved the building plans Zoning is will to provide and over-the-counter review. Call or email to schedule this review. 6. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
11/07/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | ALL RESUBMITTAL COMMENTS ARE IN CAPS SHEET SG-1 1. OK 2. OK SHEET SG-2 3. OK 4. OK 5. OK 6. OK SHEET SG-3 7. OK SHEETS A1.1, A2.1, A3.1, A4.1 and A5.1 8. OK 9. OK. 10. Provide detectable warning strips at all marked crossings as required by 2009 ICC A117.1, Sections 406.12, 13 and 14. THIS PROJECT IS A COMMERICAL PROJECT AND IS SUBJECT TO THE REQUIREMENTS OF THE 2012 IBC. ALL BUILDINGS ARE TO BE ACCESSIBLE AND CONNECTED WITH ACCESSIBLE ROUTES WITH MARKED CROSSINGS AT ALL ACCESSIBLE ROUTES CROSSING A PAAL AND SHALL HAVE DETECTABLE WARNINGS AS REQUIRED BY THE 2009 ICC A1171., SECTIONS 406.12, 13 AND 14 AS APPLICABLE. SHEET S-1 11. OK 12. At detail 7/S-1, reference is made to having 2% slope at all accessible units. All units are to be accessible. REFERENCE RESUBMITTAL 10 ABOVE. SHEETS S-2, S-3, S-4, S-5 and S-6. 13. OK 14. OK ADDITIONAL 15. RELOCATE THE 4 ACCESSIBLE PARKING SPACES AS REQUIRED BY THE 2012 IBC, SECTION 1106.6 WHICH REQUIRES THE LOCATION TO BE ON THE SHORTEST ACCESSIBLE ROUTE OF TRAVEL OF ADJACENT PARKING TO AN ACCESSIBLE BUILDING ENTRANCE. END OF RESUBMITTAL REVIEW |
11/14/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
11/21/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
11/21/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Comment not addressed; the drawing shall correctly show how the plumbing utilities are to be installed. [Initial comment: The water supply to the building, as shown on the plumbing plan on sheet P1.1, is a ¾" service but the water pressure calculations on the same sheet call for a 1" water meter and a 1" water service to the building. Development plan sheet 2 of 19 indicates a single 1" water meter serving buildings 16, 17, 18, and 19. Coordinate the site drawing, the water calculations, and the plumbing plan. Show the size and location of the reduced pressure backflow preventer assembly (detail 1/P1.2 appears to indicate that the reduced pressure backflow preventer assembly may be located within the building). Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Reference: Section 107.2.1, IBC 2012 and Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://cms3.tucsonaz.gov/sites/default/files/water/docs/backflow-ordinance.pdf] 2. Comment not addressed. [Initial comment: Coordinate the waste and vent riser diagram with the plumbing plan for both geometry and pipe sizes. Reference: Section 107.2.1, IBC 2012.] 3. Show how the exposed pipes will be protected from freezing; citing the code section alone is not adequate. [Initial comment: Show how the exposed water pipes and the water pipes in the un-heated building are to be protected from freezing. Reference: Section 305.4, IPC 2012.] 4. The specified water heater will not start functioning until the water flow exceeds 0.7 GPM but Arizona State law limits the lavatory flow rate to 0.5 GPM. In addition, the maximum water temperature for public lavatories is 110 degrees Fahrenheit. [Initial comment: Show how the temperature of the hot water supply to the public lavatories is to be controlled. Reference: Sections 416.5 and 607.1, IPC 2012 and Section C404.3, IECC 2012.] 5. The use of flush tank water closets reduces the total demand to the building but the demand (assuming one hose bibb is installed) still results in a minimum water service line of 1" being required for this building. [Initial comment: Revise the water supply piping calculations to coordinate with the plumbing design for the building. Note that the specified water closet has a flush valve. Reference: Sections 604.1 and 604.3, IPC 2012.] 6. The plumbing notes call for the domestic water to be in "Ploybutylene [sic] piping"; too close to Polybutylene.[Initial comment: Polybutylene is not approved for use in a water distribution system. Reference: Section 605.4, IPC 2012.] 7. Specify the backwater valve to be used and show how access is to be provided to the backwater valve. [Initial comment: Backwater valves are required to be installed in the building drains serving fixtures located on floors that are less than 12" above the rim of the next upstream manhole. Specify the backwater valve to be used and show how access is to be provided to the backwater valve. Reference: Sections 715.1 and 715.5, IPC 2012.] |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/25/2013 | SHANAE POWELL | OUT TO CUSTOMER | Completed |
11/25/2013 | CPIERCE1 | REJECT SHELF | Completed |