Review Date Reviewer's Name Type of Review Description Status Comments
08/04/2014 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T13CM05876
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide revised plans and calculations, highlighting any changes or with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL NOTES:

1. All SFR and Duplex plans submitted after July 1, 2009 require a solar photo-voltaic system, or future installation preparation City of Tucson Ordinance #10549 with the following provisions: 1. A 4 square feet area for (meter, disconnect & inverter) equipment adjacent to the electrical service panel or near the proposed collector panel space. 2. The best roof space available for accommodating PV solar collector panels with capacity for collector dead loading (typically 4 lbs/SF). 3. A minimum 3,800 volt-ampere PV electrical load entry on the Service Load Calculation (Show as a continuous load of 15.8 A). 4. An Electrical Panel Schedule with a 240 volt circuit breaker space labeled "reserved for Photo Voltaic". Show appropriate notation.

STRUCTURAL PLANS:

1. Provide a single member header schedule consistent with Table 602.7.1.
a. This header method is limited to a minimum size of 2 x 8, therefore the H1 size of 2 x 6 (sheet #7) is undersized.
b. The 2 x 8 size may span no more than 4'-2" at 28' (or 4'-10" at 20') building width with no snow load. The H2 2x8 is therefore undersized at 5' and 6' openings.

PLUMBING PLANS:

1. Show a plumbing code recognized by the City of Tucson, 2012 IRC. Remove the UPC reference, sheet #3.

MECHANICAL PLANS:

1. Provide (an HVAC system with) whole-house mechanical ventilation with continuous or a minimum controlled intermittent airflow rate, R303.4 & M1507.3. Show a source of outside supply air.
2. Provide Manual J/S/D calculations in accordance with M1401.3, M1601.1. Systems shall be sized in accordance with Manual S based on building loads calculated in accordance with Manual J and duct systems sized in accordance with Manual D.
3. The mechanical system calculations may be provided by deferred submittal. The deferred calculations must be approved through revision process prior to mechanical inspections.
4. Show dryer vent size and location for venting to exterior, M1501.

ELECTRICAL PLANS:

1. Revise the electrical load calculation showing a minimum 3,800 volt-ampere or 16 A continuous load entry for future Photo Voltaic equipment.
2. The double breaker space for future Photo Voltaic on the panel schedule does not require the installation of a circuit breaker.
3. Show or notate the requirement for a carbon monoxide detector outside of bedroom doors, when the dwelling includes an attached garage or gas appliance, R315.
4. Update the panel schedule descriptions by removing unused circuits #1, 6B & 8B, E3404.12 & E3706.2
5. Protect all 15A & 20A proposed outlets (except bathrooms and kitchen) including receptacles, lights and smoke detectors with combination type arc-fault circuit interrupters, E3902.12. Update the * marking on the panel schedule, or remove the marking if updating the notation for identify the requirement.
6. Show or notate a disconnect means or a locking breaker for the water heater, E4101.5.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review