Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T13CM05861
Parcel: 12509141A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM05861
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/03/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied NONE OF THE PREVIOUS COMMENTS WERE ADDRESSED IN THIS REVIEW. THOSE PREVIOUS COMMENTS FOLLOW:
1. SHEET A100: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE NOTES.
2. SHEET A102.1; PARTITION NOTES: VERIFY NOTES 2, 12, AND 22. VERIFY ALL NOTES LISTED ARE APPLICABLE TO THIS PROJECT.
3. SHEET A407; ELEVATIONS 2 AND 9: ADD A VERTICAL GRAB BAR IN THE RESTROOM PER THE ICC/ANSI A117.1 FIGURE 604.5.1.
4. SHEET A703; ELEVATIONS 1, 4, AND 5: THE CLEAR HEIGHT TO THE BOTTOM OF THE SIGNS SHOULD BE 84". REVISE.
5. GENERAL: REVIEW ALL LETTERING TO ENSURE THE MINIMUM HEIGHT OF 3/32" IS MET ON ALL SHEETS OF THIS PROJECT.
6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
10/09/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
10/14/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2012, for business occupancy (i.e. a service sink).
2. Verify that the specified temperature mixing valve is listed for use with the emergency eyewashes. Reference: Section 303.4, IPC 2012.
3. Verify that the tempered water for the lavatories is supplied using approved devices conforming to ASSE 1070 (the model number for the specified mixing valve is not shown in the Symmons literature as meeting ASSE 1070). Reference: Sections 416.5 and 607.1.2, IPC 2012.
4. The developed length of the hot water supply piping appears to be greater than fifty feet; provide a method for maintaining the temperature of the hot water supply system. Reference: Section 607.2, IPC 2012.
5. Coordinate detail 2/P1 with the waste and vent riser diagram. Provide accessible cleanouts in the island sink vent system to permit rodding of all portions of the vents located below the flood rim of the fixture (not complete in the detail but correct in the riser diagram). The riser diagram does not show the lowest point of the vent connecting to the drainage system; the detail shows this correctly. Reference: Section 916.3, IPC 2012.
10/14/2013 ROBERT SHERRY WATER REVIEW Denied 1. Tucson Water limits a 5/8" meter to a maximum demand of 15 GPM. Your design shows a demand that is in excess of 22 GPM not including the demand due to the vacuum pump and the emergency eyewashes. Provide a letter from Tucson Water confirming that the use of a 5/8" water meter will be allowed for this project.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/16/2013 SHANAE POWELL OUT TO CUSTOMER Completed
10/16/2013 CPIERCE1 REJECT SHELF Completed