Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM05833
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/08/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET TS1; CODE STUDY: THE OCCUPANCY LOAD (SEE #6) USES A FACTOR OF 20 TO DETERMINE THE NUMBER OF OCCUPANTS. WHERE IN THE IBC TABLE 1004.1.2 IS THAT FACTOR USED? VERIFY. |
| 10/08/2013 | ROBERT SHERRY | WATER | REVIEW | Passed | |
| 10/08/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 10/08/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 10/08/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not resolved; specify the anchors to be used to attach the fan coil. Show how the mechanical equipment is to be connected to the building structure (detail 2/M1) |