Permit Number: T13CM05833
Parcel: 11706175A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM05833
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/23/2013 STEVE SHIELDS ZONING REVIEW Approved
09/23/2013 JASON GREEN ENGINEERING REVIEW Approved
09/24/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13cm05833
350 E Congress #120

1. Sheet A1 shows 2 new service panels, provide a discription by way of one line diagrams showing service entrance conductors, where they originate from,grounding system, voltage and amperage discriptions. The Hvac equipment cannot be permitted untill electrical information for equipment provided such as circuit identification,
conductor sizes, disconnect sizes etc.

Ray T Majuta
Elect Plan Review
9/24/2013
520/837/4988
09/24/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Where is FC-1 to be located?
2. Show how the mechanical equipment is to be connected to the building structure (detail 2/M1)
09/24/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET TS1; CODE STUDY: THE OCCUPANCY GROUP IS CALLED OUT AS M (SEE #3), WHILE THE GENERAL BUILDING SUMMARY LISTS THIS AS A-2. COORDINATE.
2. SHEET TS1; CODE STUDY: THE OCCUPANCY LOAD (SEE #6) INDICATES A MERCANTILE USE. THE OCCUPANCY LOAD IS THEN CALCULATED ON AN ASSEMBLY USE. COORDINATE.
3. SHEET A1; WALL TYPES 6A AND 6B: THE DEMISING WALLS REQUIRE ONE LAYER OF TYPE X GYPSUM BOARD ON EACH SIDE OF THE WALL. REVISE.
4. SHEET A1; FLOOR PLAN: A NOTE AT THE EAST DEMISING WALL REFERENCES DETAIL 2/A1. REVISE.
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
09/24/2013 ROBERT SHERRY WATER REVIEW Passed
09/24/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Clarify the scope of the new work and expand the cryptic notes (e.g. "new drain line to existing stub line", "new gas line sub out").
09/24/2013 KEN BROUILLETTE FIRE REVIEW Approved
09/24/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/08/2013 GERRY KOZIOL WWM REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
10/08/2013 SHANAE POWELL OUT TO CUSTOMER Completed