Permit Number: T13CM05815
Parcel: 13803031T

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T13CM05815
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/23/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET x1: FINISH THE LEGAL DESCRIPTION AND THE PROJECT TEAM DESCRIPTION.
2. SHEET x1: PROVIDE CURRENT CODES ON THE PLAN USED IN THIS PROJECT.
3. SHEET a1; REFERENCE FLOOR PLAN: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE SECTION CUTS.
4. SHEETS a2, a3, AND a4; KEYNOTES: ADD A NOTE THAT KEYNOTES MAY BE LOCATED ON OTHER SHEETS.
5. SHEET a2; KEYNOTES: FINISH NOTES 7, 10, 13, 14, AND 15.
6. SHEETS a5, a6, AND a7; KEYNOTES: ADD A NOTE THAT KEYNOTES MAY BE LOCATED ON OTHER SHEETS.
7. SHEETS a5, a6, AND a7; KEYNOTES: FINISH NOTE 11.
8. SHEET a5; SECTION 3: FINISH THE DETAIL REFERENCES.
9. SHEET a6; SECTION 5: FINISH THE DETAIL REFERENCES.
10. SHEET a7; SECTION 7: FINISH THE DETAIL REFERENCES.
11. SHEET S4.0; DETAIL 502: PROVIDE THE ELEVATION OF THE TOP OF THE NEW STEEL COLUMN, OR REFERENCE THE ARCHITECT (ARCHITECT DOES NOT PROVIDE ON DRAWINGS).
12. SHEET S4.0; DETAILS 401, 403, AND 404: WHAT ELEVATION ARE THE FOOTINGS (TOP OR BOTTOM)? PROVIDE A NOTE ON THE DETAILS.
13. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
09/23/2013 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/24/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
10/09/2013 JASON GREEN ENGINEERING REVIEW Approved
10/09/2013 MARTIN BROWN FIRE REVIEW Approved
10/09/2013 FRODRIG2 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/09/2013 FERNE RODRIGUEZ OUT TO CUSTOMER Completed