Permit Number: T13CM05759
Parcel: 133383000

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T13CM05759
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/18/2014 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T13CM05759
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide revised plans and calculations, highlighting any changes or with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL NOTES:

1. Limit all code references to those recognized by the City of Tucson. Adopted 2012 codes are listed at the Planning & Development Services web site. Update the code referenced at the General Notes #1.

STRUCTURAL PLANS:

2. Specify the manufacturer and model of the structure. Provide specifications with required fastener methods for structural and sheathing components, R301.1.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
02/19/2014 ELIZABETH EBERBACH ENGINEERING REVIEW Reqs Change DATE: February 20, 2014
TO: Rene Martinez-Flores, P.E.
SUBJECT: 10601 E CALLE NOPALITO Grading Plan Resubmittal Review
LOCATION: Rancho Del Este lot 283
REVIEWER: Elizabeth Leibold P.E.
ACTIVITY NUMBER: T13OT01453 AND T13CM05759

Summary: Engineering Division has reviewed the re-submitted plans and drainage statement under permits T13OT01453 AND T13CM05759. Engineering does not recommend approval of either permit until the following comments are addressed.

COMMENTS:
1) Tech Man Sec.4-04.2.2.5.A: Revise drainage statement to clarify FFE based on WSEL adjacent to proposed structure, including datum conversion for NGVD29 datum shift.
2) Tech Man Sec.4-04.2.3.1.5.B: Address the following drainage statement comments:
i) Fence appears to cross the wash and therefore shall show that 100-yr flows are conveyable beneath fence. Provide cross sectional analysis with flowrate computation for 100-yr conveyance under fence opening or revise location of fence on plans.
ii) Clarify proposed fence clearances on plans. Indicate the location of the proposed elevations of openings on the details and or planviews.
iii) Provide discussion and engineering justification in drainage statement regarding whether Erosion Hazard Setback is recommended or impacting proposed development. Analysis should be based on computed flowrate for 100-yr event. Also label EHS on plan view.
iv) There is also a reference to 42 inches for scour depth but no calculation was provided. Provide scour calculations referenced in statement.

I can be reached at 837-4934 if you have questions.

Elizabeth Leibold, P.E., CPM, CFM
Civil Engineer
Engineering Division
Planning & Development Services Department
City of Tucson

Final Status

Task End Date Reviewer's Name Type of Review Description
07/09/2014 SHANAE POWELL OUT TO CUSTOMER Completed
07/09/2014 SHANAE POWELL REJECT SHELF Completed