Permit Number: T13CM05749
Parcel: 12801033A

Address:
6211 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM05749
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/18/2013 DAVID RIVERA ZONING REVIEW Approved
09/18/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/18/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM05749

1. Water Heater on sheet P2.1 is 6 KW 203/1 phase, the panel schedule shows 20 amp single pole breaker with
1.5 Kw load.

Ray T Majuta
9/18/2013
09/18/2013 ROBERT SHERRY WATER REVIEW Approved
09/18/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A1.1 (FLOOR PLAN); SHEET S1.1 (ROOF FRAMING PLAN): THE SERVICE CLOSET INDICATED ON SHEET A1.1 DOES NOT MATCH THE LOCATION SHOWN ON SHEET S1.1. CLARIFY.
2. SHEET A2.1 (DETAILS 4 AND 5); SHEET S1.1: THE STORE FRONT DETAILS INDICATE A MASONRY LINTEL OVER THE NEW OPENING, WHILE THE STRUCTURAL PLAN INDICATES A STEEL BEAM OVER THE OPENING. CLARIFY.
3. SHEET S1.1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE STRUCTURAL NOTES.
4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
09/18/2013 JASON GREEN ENGINEERING REVIEW Approved
09/18/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
09/18/2013 KEN BROUILLETTE FIRE REVIEW Approved
09/18/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/24/2013 AROMERO4 WWM REVIEW Needs Review