Permit Number: T13CM05741
Parcel: 132150190

Address:
825 E 47TH ST

Review Status: Active

Review Details: COMMERCIAL - TI

Permit Number - T13CM05741
Review Name: COMMERCIAL - TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
09/18/2013 MICHAEL ST. PAUL ZONING REVIEW Approved
09/18/2013 ANY MECHANICAL-COMMERCIAL REVIEW Active
09/18/2013 ANY PLUMBING-COMMERCIAL REVIEW Active
09/18/2013 ANY WATER REVIEW Active
09/18/2013 ANY FIRE REVIEW Active
09/18/2013 ANY WWM REVIEW Active
09/18/2013 ANY ENGINEERING REVIEW Active
10/15/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Provide 2 x 3 drawings
2. Show existing building conditions
3. Show toilet accessibility details and elevations
4. Provide structural calculations for room top mounted HVAC equipment.
5. Provide Plumbing drawings
6. Provide plans for entrire 3380 s.f. office/warehaouse space
END OF REVIEW
10/15/2013 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/05/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM05741
825 E 4th
Office Warehouse

1. Provide electrical which shows how circuited.
2. Provide a panel including placement of circuits, circuit breaker sizes, individual circuit loads and total panel loads.
3. Show a panel location. Is it a new panel ?
4. Indicate wiring method type.
5. Indicate the restroom receptacle GFCI type.
6. The Instaneous Type water heater to have a disconnect at Inst WH location.
7. Describe the type fixtures to be used.


Ray T Majuta
Elect Plan Review
PDSD, Tucson
520-837/4988
Ray.Majuta@tucsonaz.gov