Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM05731
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/18/2013 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 09/18/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Verify the termination point of the roof drains. Condensate drains may not terminate over a roof drain unless the roof drain itself terminates at or above grade in an area capable of absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2012, as amended by the City of Tucson. |
| 09/18/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 09/18/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/18/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/18/2013 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 09/18/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | An approved 2-way cleanout fitting is allowed to be used at the junction of a building drain and a building sewer; otherwise, cleanouts shall open to allow cleaning in the direction of flow (see P103). Reference: Sections 708.3.5 and 708.5, IPC 2012. |
| 09/18/2013 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 09/19/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 10/11/2013 | FRODRIG2 | WWM | REVIEW | Completed |