Permit Number: T13CM05691
Parcel: 138080170

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU

Permit Number - T13CM05691
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/25/2013 DAVID RIVERA ZONING REVIEW Denied P&DS TRANSMITTAL


FROM: David Rivera, Principal Planner

PROJECT: T13CM05691
766 W Santa Maria Street
Carport addition without permits - DDO Required for East Setback


TRANSMITTAL: September 25, 2013


COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).


This site is located in the R-1 zone (UDC 4.7.8). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure's wall facing each interior property line (Table 6.3-2.A).

The required building setback for the carport along the east property line is 6'-0" based on a wall height of 9'-0". The owner proposes 1'-0". Overhang is at property line. Overhang must be trimmed to wall otherwise a Board of adjustment would be required.
09/25/2013 LAITH ALSHAMI ENGINEERING REVIEW Approved
09/25/2013 DAVID RIVERA NPPO REVIEW Passed
09/25/2013 DRIVERA1 BUILDING-RESIDENTIAL REVIEW Needs Review