Permit Number: T13CM05643
Parcel: 127041110

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T13CM05643
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/21/2013 RAFAEL CANCINO BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS

Date: November 22, 2013
Activity: T13CM05643
Address: 5002 E. Hawthorne
Applicant: Mr. David Thompson


Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide revised plans and calculations, highlighting any changes or with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

The City of Tucson adopted the 2012 IRC with amendments on 1/1/2012. Show the code references on the plans.

GENERAL NOTES:

" Limit all code references to those recognized by the City of Tucson. Adopted 2012 codes are listed at the Planning & Development Services web site. Show the code references used for the design.
" Include Home Design Standards

PLUMBING PLAN:

1. Provide additional clean outs at main sewer line (3") quarter turns.

ROOF FRAMING PLAN:

1. Provide note specifying "trusses to be manufactured by state certified truss manufacturer."


ELECTRICAL PLAN:

1. Clarify load calculations for guest bedroom.
2. Rename sub-panel "A" to sub-panel "Guest Bedroom".

DETAIL PLAN:

1. Detail 13, change table to Table R603.7 (1) per 2012 IRC.
2. Detail 16, specify how 2X8 ledger is fastened to studs.

MECHANICAL PLAN:

1. Provide dryer vent in guest bedroom.

If you have any questions please contact:

Rafael Cancino
(520) 909-4891
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/22/2013 FERNE RODRIGUEZ OUT TO CUSTOMER Completed
11/22/2013 CPIERCE1 REJECT SHELF Completed