Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T13CM05628
Parcel: 12801005H

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T13CM05628
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/21/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
12/02/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
12/10/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not resolved; this activity is only partly an alteration of an existing building, it is also an addition to the building. Revise the envelope compliance certificate to show that the addition complies with the current energy code. Provide the supporting documentation for the "other" components noted in the envelope compliance certificate. Provide sufficient detail on the drawings to evaluate the energy compliance of the additions to the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Complete the Envelope Compliance Certificate by checking the appropriate line items in Section 3, the Air Leakage, Component Certification, and Vapor Retarder Requirements. Complete the Mechanical Compliance Certificate by checking the appropriate line items in Section 4, the Requirements Checklist. [Initial comment: Demonstrate energy code compliance for the addition to the building envelope and all new mechanical equipment using calculations based on the current code. Provide sufficient detail on the drawings to evaluate the energy compliance of the additions to the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C101.4.3, C101.5, and C103.2, International Energy Conservation Code 2012.]
2. Show that each rooftop unit has a thermostatic control that provides for off-hour and set-back control, automatic shutdown and start-up control and, if the control does not require manual changeover from the heating and cooling modes, restricts set point overlap. Reference: Section C403.2.4, IECC 2012. [Initial comment: Show that the proposed HVAC system meets the control requirements of Sections C403.2.4 and C403.3. Reference: Section C303.1, International Energy Conservation Code 2012.]
12/10/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Verify that the expansion and contraction of the hot water CPVC piping will be accommodated. [Initial comment: Revise the specified pipe/tubing support spacing shown in detail 15/P1.2 to comply with the intervals shown in Table 308.5, IPC 2012 for the materials being used. Verify that the expansion and contraction of the hot water CPVC piping will be accommodated. Reference: Section 308, IPC 2012.]
2. The size of a circuit-vented horizontal branch drain is determined by the total drainage load (fixture units) served by that horizontal branch drain plus any additional drainage load from upstream branches. Table 710.1(2), IPC 2012 limits a 3" horizontal branch to a maximum of 20 fixture units and the entire length of each circuit-vented horizontal branch shall be uniformly sized for the drainage load it serves (Section 914.3, IPC 2012). [Initial comment: Revise the size of the combination drain and vent pipe in the bar area to correspond to the requirements of Table 915.3, IPC 2012.]
3. A second hand sink was added to the bar area due to the Health Department review; it does not appear to have been added to the plumbing plans.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/20/2013 FERNE RODRIGUEZ OUT TO CUSTOMER Completed
12/20/2013 CPIERCE1 REJECT SHELF Completed