12/18/2013 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 12-19-13
Activity: T13CM05613
Address: 1025 N. Perry Av
Applicant: Leonard Gonzales

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. The City of Tucson has adopted the 2012 International family of codes. As of 1/01/2013 all code references should refer to the currently adopted code or appeal must be made to the Building Official for alternate code use. 2006 IRC note 8 sheet 7.

SITE PLAN:
2. Specify the location of all utility lines, R106.1.1.

FLOOR PLAN:
3. Provide sufficient emergency escape/rescue openings from sleeping rooms, R310. Minimum clear opening = 24" high x 20" wide.
4. Specify cement, fiber-cement, or glass-mat board backing in tub/shower enclosures, R307.2, R702.4.2.

STRUCTURAL / FRAMING PLAN:
5. Provide a complete braced wall line layout showing the location of braced wall panels within 10 feet of each end of each braced wall line and shall be no more than 20 feet apart, R403.1.6, R602.10.2.2.

SECTIONS - DETAILS:
6. Correct mislabeled section detail references.
7. Show ceiling insulation applied tight to roof sheathing or provide an attic space ventilation calculation and indicate the location of attic vents.

PLUMBING PLAN:
8. Correct water conservation requirements: Sinks = 2.2 gpm, Showerheads = 2.5 gpm, P2903.2.
9. Clarify water supply piping material 'aqua pec'
10. Specify the maximum developed length of water line from the meter the furthest appliance served, and the lowest available working pressure, P2903.7.

MECHANICAL PLAN:
11. Provide Manual J/S/D calculations for the forced air unit in accordance with M1401.3, M1601.1.

ELECTRICAL PLAN:
12. All outlets specified in section E3902.12 shall be protected with combination-type arc-fault breakers (not just bedroom outlets).
13. Specify faceplate grounding per E4001.11.1.
14. Specify tamper resistant receptacles per E4002.14.

INTERNATIONAL ENERGY CONSERVATION CODE:
15. Specify a "U" factor and solar heat gain coefficient of the windows and doors that meets or exceeds the requirements of N1102.1. The simplified prescribed energy value for climate zone 2B glazing is U=0.40 and skylights is U=0.65, the default SHGC is 0.25.
16. Show hot water pipe with minimum R-3 insulation, N1103.4.2.