Permit Number: T13CM05545
Parcel: 126192020

Address:
4303 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM05545
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/12/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET S1.0; STRUCTURAL CALCULATIONS: A BEAM ON THE EAST WALL (IN THE SOUTHEAST CORNER) IS DENOTED AS A B-3 ON THE PLAN (2-2X10), WHILE THE CALCULATIONS INDICATE A B-2 (5 1/8" X 10 1/2" GLU-LAM). CLARIFY.
09/12/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show the required U-factor and SHGC values for the new storefront and glazing on the drawing.