Permit Number: T13CM05545
Parcel: 126192020

Address:
4303 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM05545
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/10/2013 STEVE SHIELDS ZONING REVIEW Approved
09/10/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show that the new storefront and doors comply with the current energy code, IECC 2012.
09/10/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Passed
09/10/2013 ROBERT SHERRY WATER REVIEW Approved
09/10/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET TS1; PROJECT DRAWING INDEX: THERE ARE NO STRUCTURAL SHEETS S1.0 AND S2.0 IN THIS SET. PROVIDE.
2. SHEET A4.0; ROOF PLAN GENERAL NOTES: NOTE 4 INDICATES A STRUCTURAL SHEET S3.0. VERIFY.
09/10/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
09/10/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/11/2013 LOREN MAKUS ENGINEERING REVIEW Approved
09/11/2013 MARTIN BROWN FIRE REVIEW Approved
09/12/2013 FRODRIG2 WWM REVIEW Passed