Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM05528
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/11/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 09/17/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | GENERAL 1. The City of Tucson standard for minimum lettering size on construction documents is 3/32" actual for both upper and lower case. The following sheets have lettering that does not comply with this standard and needs to be revised and resubmitted: A-01, A-02, A-03, M-02, M-REF, E-01, E-02 and E-04. 2. Provide structural calculations and structural details for the wall mounted water heater. Please include partition analysis. SHEET CS-01 3. Delete project data code reference to Arizonans with Disabilities Act. SHEET A-00 4. Delete all ADAAG references and associated details. Reference instead to the 2012 IBC, Chapter 11 and the 2009 ICC A117.1 and all accessibility requirements and details. END OF REVIEW |
| 09/19/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 09/23/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/23/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide structural calculations for the mounting shelf for the water heater to show that the water heater will be safely supported. Reference: Section 301.2, IPC 2012. 2. Clarify the backflow specifications for the carbonated beverage dispensers. The backflow device note on the plumbing plan (P-01) and the beverage center backflow schematic (P-02) both call for an ASSE 1013-listed reduced pressure backflow assembly for the carbonated beverages but the note on the fixture connection schedule calls for an ASSE 1022-listed dual check valve. 3. The sanitary waste diagram on sheet P-02 shows a dry-vented fixture drain connecting to the vent for a water closet, as if the fixture drains were connected at different levels with a common vent. Show that each trap and trapped fixture has been vented in accordance with one of the methods shown in the IPC. Reference: Section 901.2.1, IPC 2012. 4. Clarify the installation of a hydromechanical grease interceptor with the vented flow control device to serve a floor sink can be installed, i.e. show how the flow control device can be installed below the floor level with ready access (defined as being able "to be directly reached without requiring the removal or movement of any panel, door or similar obstruction") and in accordance with the manufacturer's instructions. Reference: Sections 202 and 1003.4.2, IPC 2012. |
| 09/23/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide the hood weight and structural calculations to show that the Type II hood is supported from the building structure in accordance with Section 507.6, IMC 2006. Reference: Section 302.1, IMC 2012. 2. Clarify the size of the all-thread rods proposed for suspending the Type II hood; they are shown as ½" on M-REF and 3/8" on sheet M-02. Reference: Section 107.2.1, IBC 2012. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/10/2013 | CPIERCE1 | REJECT SHELF | Completed |