Review Details: REVISION - - 2ND

Permit Number - T13CM05521
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/05/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Replacement of the two heat pumps constitutes new work. Provide heating and cooling load calculations and verify that the heating and cooling capacities of the units do not exceed the load requirements. Show that the units comply with Sections C403.2 and C403.3, IECC 2012 (e.g. submit a mechanical compliance certificate from COMcheck with the appropriate check boxes filled in).