Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T13CM05521
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/05/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Replacement of the two heat pumps constitutes new work. Provide heating and cooling load calculations and verify that the heating and cooling capacities of the units do not exceed the load requirements. Show that the units comply with Sections C403.2 and C403.3, IECC 2012 (e.g. submit a mechanical compliance certificate from COMcheck with the appropriate check boxes filled in). |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/06/2013 | SHANAE POWELL | APPROVAL SHELF | Completed |
11/06/2013 | SHANAE POWELL | OUT TO CUSTOMER | Completed |