Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T13CM05521
Parcel: 12902090A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM05521
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/09/2013 STEVE SHIELDS ZONING REVIEW Approved
09/09/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved 1. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted The exhausted air from the restrooms shall be limited to no more than 10% of any subsequent supply air stream. Reference: Section 403.2.1 (4), IMC 2012.
2. Revise the mechanical design as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2012.
09/09/2013 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
09/09/2013 ROBERT SHERRY WATER REVIEW Approved
09/09/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved 1. Provide Site Plan.
2. Provide structural details and calculations for wall mounted 20 gallon water heater. Please include wall analysis.
END OF REVIEW
09/09/2013 GERRY KOZIOL WWM REVIEW Approved
09/09/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved The developed length of the hot water supply piping appears to be greater than fifty feet; provide a method for maintaining the temperature of the hot water supply system. Reference: Section 607.2, IPC 2012.
09/09/2013 JASON GREEN ENGINEERING REVIEW Approved
09/09/2013 KEN BROUILLETTE FIRE REVIEW Approved
09/09/2013 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
09/12/2013 CPIERCE1 APPROVAL SHELF Completed