Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM05521
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/09/2013 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 09/09/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | 1. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted The exhausted air from the restrooms shall be limited to no more than 10% of any subsequent supply air stream. Reference: Section 403.2.1 (4), IMC 2012. 2. Revise the mechanical design as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2012. |
| 09/09/2013 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 09/09/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/09/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | 1. Provide Site Plan. 2. Provide structural details and calculations for wall mounted 20 gallon water heater. Please include wall analysis. END OF REVIEW |
| 09/09/2013 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 09/09/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | The developed length of the hot water supply piping appears to be greater than fifty feet; provide a method for maintaining the temperature of the hot water supply system. Reference: Section 607.2, IPC 2012. |
| 09/09/2013 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 09/09/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 09/09/2013 | RONALD BROWN | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/12/2013 | CPIERCE1 | APPROVAL SHELF | Completed |