Permit Number: T13CM05500
Parcel: 13014447A

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T13CM05500
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/10/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. GENERAL: PROVIDE TWO SETS OF THE JOIST DESIGN CALCULATIONS.
2. GENERAL: PER THE IBC SECTION 107.3.4.1, DEFERRED SUBMITTALS WILL BE REVIEWED BY THE REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE, WHO SHALL REVIEW THE DRAWINGS AND FORWARD THEM TO THE BUILDING OFFICIAL WITH A NOTATION (ON THE DRAWINGS AND ON THE CALCULATIONS) THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO THE BUILDING DESIGN. PROVIDE.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/29/2014 CPIERCE1 REJECT SHELF Completed