Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T13CM05500
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/08/2013 | STEVE SHIELDS | ZONING | REVIEW | Denied | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: New Office Building - 1305 S. Alvernon Way. T13CM05500 Building Plan (1st Review) TRANSMITTAL DATE: October 8, 2013 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 3. Until the development package has been approved the building plans cannot be approved. 4. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
| 10/08/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T13CM05500 New Office Bldg, Progressive 1305 S Alvernon 1. Last review requested a fault current analysis, only provide fault current values at service, panels and HVAC equipment. Provide a complete fault current analysis showing how breakdown occurs beginning at service and on to all panels. If Series Rated systems or fully rated breakers need to be used please indicate on plan. Ray T Majuta Elect Plan Review PDSD, Tucson 10/9/2013 Ray.majuta@tucsonaz.gov 520-837-4988 |
| 10/11/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/15/2013 | LOREN MAKUS | ENGINEERING | REVIEW | Denied | The development package must be approved first. |
| 10/15/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approv-Cond | AN AUTOMATIC FIRE SPRINKLER SYSTEM DESIGNED TO NFPA 13 WILL BE INSTALLED PER OWNER. |
| 10/16/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 10/16/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/16/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The floor drains in the MDF room and the men's restroom are now shown with horizontal vents below the floor level. [Initial comment: Verify that all of the vents within the building rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2012.] 2. The new vent has been shown upstream of the sand/oil separator; relocate the vent to the downstream side of the separator. [Initial comment: Provide a vent downstream of the sand/oil separator to protect the seal for the sand/oil interceptor. Reference: Section 1003.9, IPC 2012.] 3. Based on Table 402.4(2), IFGC 2012, some of the gas pipes are undersized (e.g. 1982 CFH requires a 4" pipe, 741 CFH requires a 2-1/2" pipe). [Initial comment: Provide natural gas pipe sizing calculations. Include the developed pipe lengths on plans. Reference: Section 402.3, IFGC 2012.] |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/30/2013 | AROMERO4 | APPROVAL SHELF | Completed |
| 10/30/2013 | AROMERO4 | OUT TO CUSTOMER | Completed |
| 10/30/2013 | CPIERCE1 | REJECT SHELF | Completed |