Permit Number: T13CM05500
Parcel: 13014447A

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T13CM05500
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/12/2013 LOREN MAKUS ENGINEERING REVIEW Denied The development package must be approved first.
09/13/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET T1.0: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE BUILDING CODE DATA.
2. SHEET A0.1 (PARTITION TYPES); SHEET A1.1 (FLOOR PLAN): ARE THE TYPICAL INTERIOR PARTITIONS TYPE G5-P/A? THERE ARE MANY INTERIOR PARTITIONS THAT HAVE NO DESIGNATION ON THE PLAN. ADD A NOTE ON THE PLAN OR DETAILS STATING INTERIOR PARTITION TYPES IF NOT INDICATED ON THE PLAN.
3. SHEET A0.1 (PARTITION TYPES); SHEET A1.1 (FLOOR PLAN): EXTERIOR WALL TYPES ARE NOT INDICATED ON THE PLAN. VERIFY. ADD A NOTE OR REFERENCE ON THE PLAN FOR EXTERIOR WALL TYPES.
4. SHEET A0.2: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE NOTES.
5. SHEET S1.1 (FOUNDATION PLAN); SPECIAL BASE PLATE BP-1 DETAIL: THIS DETAIL REFERENCES GRIDS C AND 13. SHOULD THIS DETAIL ALSO INCLUDE GRIDS G AND 13? VERIFY.
6. SHEET S1.1 (FOUNDATION PLAN); SECTIONS 1, 3, AND 15/S1.2: DEFINE ON THE FOUNDATION PLAN OR THE SECTIONS (OR BY REFERENCE NOTE) THE WIDTH OF THE TYPICAL WALL FOOTINGS.
7. SHEET S1.2; SECTION 5: PROVIDE THE WIDTH AND DEPTH OF THE THICKENED SLAB ON THE SECTION, OR WITH A REFERENCE NOTE ON THE DRAWINGS. THE TYPICAL DETAIL ON SHEET S0.1 INDICATES A THICKENED SLAB FOR A STUD WALL.
8. SHEET S1.2; SECTION 4: A COORDINATION NOTE IS IDENTIFIED BY AN ASTERISK. IS THIS IN RELATION TO THE THICKENED SLAB WIDTH AND DEPTH? INDICATE THAT ON THE SECTION.
9. SHEET S2.1; ROOF FRAMING PLAN: TWO TUBE COLUMNS JUST EAST OF GRID LINE 15, BETWEEN GRIDS F AND G, ARE NOT IDENTIFIED. PROVIDE.
10. SHEET S2.2; SECTION 3: IS THE C12X20.7 INDICATED ON THE SECTION CORRECT? THE ROOF FRAMING PLAN SHOWS A C6X8.2. VERIFY.
11. SHEET S2.2; SECTION 3: AT THE C12X20.7, THE NOTE INDICATES TO WELD TO THE BEAM. SHOULD IT ALSO INCLUDE WELDING AT THE JOISTS? VERIFY AND REVISE NOTE AS REQUIRED.
12. SHEET S2.3; SECTION 11: INDICATE ON THE SECTION THE BRACE SIZE, SPACING, AND CONNECTION TO THE JOIST AND TO THE VERTICAL STUD.
13. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
09/16/2013 ROBERT SHERRY WATER REVIEW Denied Reduced pressure backflow prevention assemblies for the water service are required to be installed in locations accessible to Tucson Water and as close as practicable to the service connection. Reference: Chapter 27, Article V, Section 27-76 (a), Tucson Code, http://cms3.tucsonaz.gov/sites/default/files/water/docs/backflow-ordinance.pdf
09/16/2013 MICHAEL ST. PAUL ZONING REVIEW Needs Review The development package (DP13-0163) must be approved.
09/17/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM05500
1305 S Alvernon Wy
Progressive Regional Offices

1. City of Tucson requires compliance by calculation with 2012 City of Tucson Outdoor Lighting Code. Provide on Sheet E1.1 or 1.2.
ODLC can be found on City web page by going to Departments, Planning and Zoning, Codes and Ordinances, to OutDoor Lighting Code. Must select an area (this site E) , then select an Option, calculate lumen out put of site lighting including building mounted lighting. Total value of lumen output not to exceed allowed value. This Outdoor Lighting also limits fixtures and lamps to 3500K color rated temperature, which could not be found on fixture schedule, please verify.
2. Per City of Tucson Commercial Submittal Requirements,provide on Sheet E5.1 a fault current analysis beginning at service on throught to panels, and indicate if a Series or Fully rated System to be used. Per C of T rqmt's.
3. Sheet E5.2, provide a grounding detail for the Pylon Sign Service and size conductor. NEC 250-30.
4. Sheet E5.2, Panel L1-14, cannot locate offices 124-127 ?

Ray T Majuta
Elect Plan Review
PDSD, City of Tucson
9/17/2013
Ray.Majuta@tucsonaz.gov
520/837/4988
09/17/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide calculations showing how the water supply piping has been sized. Reference: Sections 604.1 and 604.3, IPC 2012.
2. Verify that the pipe sizes called out for the flush valves will not result in water velocities greater than that recommended by the pipe manufacturer (e.g. limit the water velocity to less than 8 FPS for copper, PEX, or CPVC piping). Reference: Table 604.3, IPC 2012.
3. Verify that all of the vents within the building rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2012.
4. The sand/oil waste collection system includes p-traps at each floor drain and at the outlet of the trench drain. Clarify how these p-traps are to be self-scouring when presented with sand-bearing waste. Reference: Section 1002.2, IPC 2012.
5. Provide a vent downstream of the sand/oil separator to protect the seal for the sand/oil interceptor. Reference: Section 1003.9, IPC 2012.
6. Provide a cleanout at the base of the roof drain stack located at column E-16 prior to connection to the horizontal storm drain. Reference: Sections 708.3.4 and 1101.8, IPC 2012.
7. Provide natural gas pipe sizing calculations. Include the developed pipe lengths on plans. Reference: Section 402.3, IFGC 2012.
09/17/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
09/17/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Complete the Envelope Compliance Certificate by checking the appropriate line items in Section 3, the Air Leakage, Component Certification, and Vapor Retarder Requirements.
2. Provide heating load calculations that justify the capacities of the heating equipment specified for use in the inspection bays. Reference: Sections C403.2.1 and C403.2.2, IECC 2012.
3. Provide justification for the use of a Zone Air Distribution Effectiveness (Ev) of 1.0 for a ceiling supply, ceiling return using a gas-fired roof top unit. (Note: the primary airflow used in the ventilation calculations for the three units is not the same as the scheduled airflow.) Reference: Section 403.3.1.2, IMC 2012.
09/23/2013 KEN BROUILLETTE FIRE REVIEW Denied 1. Based on the square footage and type of construction, your required fire flow for this project is 2,750 GPM for 2 hours duration at 20 psi residual pressure per Appendix B of the 2012 IFC. You need three fire hydrants per Appendix C of the 2012 IFC. Please indicate on site plan the location of the proposed fire hydrant and any existing fire hydrants to see if they meet distance requirements.
2. Please indicate how you are meeting the access controlled provisions in Chapter 10 Section 1008 with the proposed access control system on egress doors.
3. The refective ceiling plan is missing required exit signage.
4. Please indicate the location of all emergency egress lighting componets.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/07/2013 CPIERCE1 REJECT SHELF Completed
09/23/2013 CPIERCE1 OUT TO CUSTOMER Completed