Permit Number: T13CM05399
Parcel: 13506136G

Address:
2540 S KOLB RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM05399
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/10/2013 MARTIN BROWN FIRE REVIEW Approved
09/12/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please provide a site plan.
2. Please provide structural calculations for all work shown on the S sheets.
3. Please provide certification of special inspectors required by the 2012 IBC, Section 1704 and your structural engineer.
END OF REVIEW
09/12/2013 ROBERT SHERRY WATER REVIEW Approved
09/12/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
09/12/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
09/17/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM05399
2540 S Kolb Rd
Oreilly Auto Parts

1. Provide a 2012 IECC Budget Lighting Calculation, ComChect ok.


Ray T Majuta
Elect Plan Review
PDSD, C of Tucson
9/17/2013
Ray.Majuta@tucsonaz.gov
520/837/4988

Final Status

Task End Date Reviewer's Name Type of Review Description
09/18/2013 CPIERCE1 REJECT SHELF Completed