Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM05387
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/30/2013 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 08/30/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 08/30/2013 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 08/30/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 08/30/2013 | KEN BROUILLETTE | FIRE | REVIEW | Denied | PLEASE INDICATE THE LOCATION OF EMERGENCY EGRESS LIGHTING |
| 08/30/2013 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/30/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/30/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A1; FLOOR PLAN (STAFF AREA): AN ELEVATION REFERENCE INDICATES 6/A3 (NEAR THE RESTROOM). REVISE THAT REFERENCE. 2. SHEET A1; FLOOR PLAN: PER THE IBC TABLE 2902.1, A HIGH/LOW DRINKING FOUNTAIN OR SINGLE POINT OF USE WATER DISPENSER IS REQUIRED. VERIFY. 3. SHEET A1; KEY NOTES: NOTE 10.1 USES A REFERENCE THAT IS NOT FROM THE 2009 ICC/ANSI A117.1. REVISE. 4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 08/30/2013 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 09/06/2013 | AROMERO4 | WWM | REVIEW | Needs Review |