Review Details: RESUBMITTAL

Permit Number - T13CM05364
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/01/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET S1.0; PLAN KEYNOTES: ONLY KEYNOTE 1 WAS LOCATED ON THE PLANS. VERIFY.
2. SHEET S2.0; SECTION 1: A SECTION NOTE REFERENCES DETAIL 3/S4.1 FOR A KNEE BRACE. REVISE THAT NOTE.
3. SHEET S2.0; SECTION 1: A NOTE INDICATES TO SEE DETAIL 2/S3.0 FOR MORE DETAIL. IS THIS CORRECT?
4. SHEET S3.0; DETAIL 2: REMOVE A LEADER LINE TO THE DIAGONAL BRACE.
5. SHEET S3.0; DETAIL 2: AT THE DIAGONAL BRACE, ADD TO THE VERBIAGE "SEE NOTE" WITH "THIS SHEET".
6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.