Permit Number: T13CM05358
Parcel: 123070460

Address:
2231 E MABEL ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T13CM05358
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/30/2013 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 9-3-13
Activity: T13CM05358
Address: 2231 E Mabel
Applicant: Kevin Osborn

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Residential Code with local amendments. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. As of 1/01/2013 the City of Tucson has adopted the 2012 International family of codes. Correct all code references to the 2006 IRC or appeal to the Building Official for alternate code use.

PLUMBING PLAN:
2. Provide a gas line isometric and size the supply pipe for the connected demand. Include the length of line and BTU demand for each appliance, size of each branch, total demand, and total developed length from meter to the most remote appliance on the system, G2413.1, Table G2413.4 (1).

MECHANICAL PLAN:
3. Based on the information provided on the construction drawings, no work to the heating and cooling system will be included on this permit.

ELECTRICAL PLAN:
4. Provide accurate code references to all electrical codes cited.
5. All outlets specified in section E3902.12 shall be protected with combination-type arc-fault breakers (not just bedroom outlets).
6. Specify faceplate grounding per E4001.11.1.
7. Specify tamper resistant receptacles per E4002.14.

INTERNATIONAL ENERGY CONSERVATION CODE:
8. Specify the "R" value of the insulation, as well as the "U" factor and the solar heat gain coefficient of the windows and doors. Tucson is in climate zone 2B. The simplified prescribed energy values for glazing and skylights is U=0.40, SHGC=0.25, ceiling R=38 and walls R=13, N1102.1.
9. Indicate how the minimum ceiling insulation value of R-38 (11.25" batt) will be installed in 2x10 rafters (9.25" cavity).

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review