Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T13CM05273
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/05/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET CA-2; FOUNDATION NOTES: NOTE 2 INDICATES FOUNDATION DESIGN BASED ON A SECTION OF THE 2006 IBC. REVISE THE SECTION TO MEET CRITERIA OF THE 2012 IBC. 2. SHEET CA-2 (FOUNDATION NOTES); GEOTECHNICAL REPORT (PAGE 15): NOTE 2 INDICATES A SOIL BEARING CAPACITY OF 2860 PSF. DOES THIS VALUE COME FROM THE RECOMMENDATIONS OF THE TABLE UNDER SECTION 5.7 OF THE GEOTECHNICAL REPORT? VERIFY. 3. SHEETS CA-2, CA-3, CA-4, AND CA-4.1: REMOVE THE REVISION CLOUDS FROM THESE SHEETS. 4. GENERAL: STRUCTURAL CALCULATIONS WERE NOT LOCATED FOR THIS PROJECT. PROVIDE. 5. GENERAL: PROVIDE WRITTEN RESPONSES FOR ALL REVIEW COMMENTS. |
| 09/11/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T13CM05273 Electrical comments on permit # T13CM05264 for Store Building. Ray Majuta Elect Plan Review 9/12/2013 |
| 09/13/2013 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/30/2013 | CPIERCE1 | REJECT SHELF | Completed |