Permit Number: T13CM05264
Parcel: 10706038A

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T13CM05264
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/27/2013 KEN BROUILLETTE FIRE REVIEW Approved none
09/05/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 3/32-inch. Reference: Section 107.2.1, IBC 2012.
2. Provide plumbing plans to a known scale (P1.1) and show the correct orientation of the building (i.e. show a north arrow in the correct direction on sheets P1.1 and P1.1.1). Reference: Section 107.2.1, IBC 2012.
3. Verify that the pipe sizes called out for the flush valves will not result in water velocities greater than that recommended by the pipe manufacturer (e.g. limit the water velocity to less than 8 FPS for copper). Reference: Table 604.3, IPC 2012.
4. An approved 2-way cleanout fitting is allowed to be used at the junction of a building drain and a building sewer; otherwise, cleanouts shall open to allow cleaning in the direction of flow. Reference: Sections 708.3.5 and 708.5, IPC 2012.
5. Show how access is to be provided to the backwater valve. Reference: Section 715.5, IPC 2012.
6. Verify that all of the vents rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. Reference: Section 905.4, IPC 2012.
09/05/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET G1.0: ADD THE STORE NUMBER AT THE MAIN TITLE REFERENCE.
2. SHEET G1.0: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE NOTES/INDEX.
3. SHEET G1.0; PROJECT DATA (SPRINKLER SYSTEM REQUIREMENTS): REFERENCE IS MADE TO THE 2006 IFC. REVISE TO THE 2012 EDITION.
4. SHEET A1.0; EXIT REQUIREMENTS: THE TRAVEL DISTANCE REFERENCES IBC TABLE 1016.1. REVISE THE TABLE REFERENCE TO THE 2012 EDITION.
5. SHEET A1.0; EXIT REQUIREMENTS: ADD A REFERENCE ON THE DRAWINGS TO THE IBC TABLE 1014.3 FOR THE COMMON PATH OF EGRESS TRAVEL.
6. SHEET A1.0; ARRANGEMENT MEANS OF EGRESS: ADD A REFERENCE ON THE DRAWINGS TO THE IBC SECTION 1015.2.1 FOR THE REQUIRED EXIT ARRANGEMENT.
7. SHEET A1.1; WATER CLOSET DETAILS D1: ON THE SIDEWALL, PROVIDE THE LENGTH OF THE VERTICAL GRAB BAR PER THE ICC/ANSI FIGURE 604.5.1.
8. SHEET A1.2; KEY NOTES: NOTE 26 INDICATES TO SEE DETAILS 1/A8.3 AND 2/A8.3 FOR THE WALL RECESS. REVISE (1/A8.3 IS A DRAFT STOP DETAIL).
9. SHEET A1.3 (FLOOR PLAN); WALL TYPES: IN THE RESTROOMS, WALL TYPES B (4/A9.1) AND E (8/A9.1) DO NOT INDICATE MOISTURE RESISTANT GYPSUM BOARD. VERIFY.
10. SHEET A1.3 (FLOOR PLAN); WALL TYPES: THE EXTERIOR WALLS DO NOT HAVE WALL TYPES INDICATED. VERIFY.
11. SHEET A4.0; SHEET A5.2: WALL SECTION 3/A5.2 IS NOT INDICATED ON SHEET A4.0. VERIFY.
12. SHEET A9.4; DETAIL 3: THE ROD SUPPORTING ANGLE IS REFERENCED AS 2-1/2" X 2-1/2" X 0.4. REVISE THE ANGLE THICKNESS.
13. SHEET S1.2 (DETAIL 10); STRUCTURAL CALCULATIONS (SHEET 8.14): THE CALCULATIONS INDICATE A 24" DIAMETER PIER, WHILE THE DRAWING INDICATES 18". CLARIFY.
14. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
09/05/2013 ROBERT SHERRY WATER REVIEW Approved
09/11/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM05264
1395 W Miracle Mile
New Cirlce K Building

1. Sheet E0.0, indication given to comply with 2008 NEC, change to 2011 NEC as on cover sheet.
2. Submittal Requirements per City of Tucson require all text lettering or numbering to be 3/32" minimum. Sheets E1.1,
E1.2, E6.0 detail 5 too small for re-printable purposes and Sire installation.
3.Sheet E1.0 concerning the lumen calculation. Please show compliance with The City of Tucson Outdoor Lighting Code by providing the following on this sheet:
a. choose a lighting area, yours will be E3
b. choose an option, some allow Full Cut Off lighting only and some allow both Full Cut Off and Unshielded,
c. list total lumen output for Full Cut Off and Unshielded,
d. determine size of area, table 401.1 allows so much lumen output for a one acre site (43,560 sq ft). Ratio your site to one acre to get allow lumens per acre of Full Cut Off and Unshielded. Must be at allowed value or below.
e. Note all outdoor lighting even if on building must be minimum 3500 K color rated temperature, could not find this on spec's sheets on E1.2, please confirm, per Outdoor Lighting Code Section 402.1.
4.Sheet E6.0, the service entrance feeders from utility to service is provided by the customer in this jurisdiction. Must provide the size and type of conductors as well as the conduit size.
5. Sheet E6.0. the TEP Utility Service Requirement Book indicates the fault current for a pad mounted transformer providing 800 amps at 120/208v to be 55,600 amps, how was the 51,502 amp value obtained ?

Ray T Majuta
Elect Plan Review
PDSD, Tucson
9/12/2013
Ray.majuta@tucsonaz.gov
520/837/4988
09/11/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Complete the Envelope Compliance Certificate by checking the appropriate line items in Section 3, the Air Leakage, Component Certification, and Vapor Retarder Requirements. Supporting documentation shall be either on the drawings or in the project manual.
2. Revise the energy code analysis for the building envelope, coordinating the building components used in the analysis with those shown on the drawing (e.g. the building has wood trusses, not steel trusses; the roof does not appear to have the R-34.6 continuous insulation called out on the COMcheck component section). Reference: Section C303.1, IECC 2012, as amended by the City of Tucson.
3. The submitted COMcheck Envelope Compliance Certificate calls for the proposed HVAC system to meet the requirements of Section C406.2, IECC 2012. Per Section C406.2, the minimum EER for a heat pump <240 MBH is 12.0. The submitted heat pumps are rated only with an EER of 1.2. Reference: Section C303.1, International Energy Conservation Code 2012.
4. Verify that the sequence of operation for the restroom exhaust fans is such that all of the air supplied to the restrooms will be exhausted (i.e. the exhaust fan shall run even if the restroom lights are off during operating hours). Reference: Section 403.2.1 (4), IMC 2012.
09/13/2013 MICHAEL ST. PAUL ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/30/2013 CPIERCE1 REJECT SHELF Completed