Permit Number: T13CM05208
Parcel: 12712267A

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T13CM05208
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/07/2013 DAVID RIVERA ZONING REVIEW Approved
11/13/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/13/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
11/14/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The water piping isometric (P4.2) still shows the four flush-valve water closets supplied with 1" pipe. The minimum flow for a siphon jet water closet is 25 GPM which will result in water velocities exceeding 8 feet per second. One note on sheet P2.2 calls for "1-1/4" CW to each WC-1" but another note on the same sheet calls for "1" CW to each WC & ½" CW to K69". In addition, The 2" CW serving 4 lavatories, 2 urinals, and 2 water closets is reduced to 1-1/2" for no apparent reason when it drops down to serve the fixtures.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/15/2013 CPIERCE1 REJECT SHELF Completed