Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T13CM05208
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/07/2013 | DAVID RIVERA | ZONING | REVIEW | Approved | |
11/13/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
11/13/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
11/14/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The water piping isometric (P4.2) still shows the four flush-valve water closets supplied with 1" pipe. The minimum flow for a siphon jet water closet is 25 GPM which will result in water velocities exceeding 8 feet per second. One note on sheet P2.2 calls for "1-1/4" CW to each WC-1" but another note on the same sheet calls for "1" CW to each WC & ½" CW to K69". In addition, The 2" CW serving 4 lavatories, 2 urinals, and 2 water closets is reduced to 1-1/2" for no apparent reason when it drops down to serve the fixtures. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/15/2013 | CPIERCE1 | REJECT SHELF | Completed |