Permit Number: T13CM05187
Parcel: 14029042A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM05187
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/27/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide construction documents that are complete and clearly indicate the extent of the proposed work (i.e. remove the "Preliminary, not for Construction" label from the drawings.). Reference: Section 107.2.1, IBC 2012.
2. Clarify the discrepancy between the specified lavatory faucets (0.50 GPM and 15 seconds per activation cycle) and the requirement to provide a 0.75 GPM aerator for each lavatory faucet (WH-4 specification). Also, how will the specified temperature mixing valve work with the thermostatically-controlled water heater?
08/27/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide construction documents that are complete and clearly indicate the extent of the proposed work (i.e. remove the "Preliminary, not for Construction" label from the drawings.). Reference: Section 107.2.1, IBC 2012.
08/27/2013 ROBERT SHERRY WATER REVIEW Approved
09/04/2013 JASON GREEN ENGINEERING REVIEW Reqs Change Building Plan cannot be approved until a DP Package has been reviewed and approved for all onsite changes as shown on the proposed site plan Sheet AS-1. Per the proposed site plan it appears that a new sidewalk is proposed to connect the building on adjacent lots. Sidewalk needs to be reviewed for ADA compliance. Also verify that all carport as seen on the 2012 aerials have a last approved site plan and delineate them on this site plan as well. JG
09/09/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. At detail 2/A3, Rooms 123 and 124, Section 1109.2.2 of the 2012 IBC, where there are 6 or more water closets or urinals provide in a toilet room, one abulatory accessible water closet compartment shall be provided.
END OF REVIEW
09/10/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
09/11/2013 MICHAEL ST. PAUL ZONING REVIEW Reqs Change Development Package required.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/12/2013 CPIERCE1 OUT TO CUSTOMER Completed
09/12/2013 CPIERCE1 REJECT SHELF Completed