Permit Number: T13CM05163
Parcel: 14117015C

Review Status: Active

Review Details: COMMERCIAL - TI

Permit Number - T13CM05163
Review Name: COMMERCIAL - TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
08/22/2013 MARTIN BROWN FIRE REVIEW Approv-Cond ONE SPRINKLER HEAD WILL BE REQUIRED IN MEDICAL GAS STORAGE ROOM. IT MAY BE SUPPLIED FROM THE DOMESTIC WATER.
08/29/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A0.0 (PROJECT INFORMATION); SHEET A1.0 (BUILDING INFORMATION); SHEET A1.0 (ALLOWABLE AREA): SHEET A0.0 AND SHEET A1.0 (BUILDING INFORMATION) LIST THE CONSTRUCTION TYPE AS VB, WHILE SHEET A1.0 (ALLOWABLE AREA) LISTS THE CONSTRUCTION TYPE AS IIB. CLARIFY.
2. SHEET A2.0 (FLOOR PLAN); FLOOR PLAN KEYNOTES: NEAR DOOR 118, THERE IS A KEYNOTE 30 INDICATED. IS THIS KEYNOTE LOCATION CORRECT? VERIFY.
3. SHEET A2.0; KEYNOTES: NOTES 11, 15, 31, AND 33 WERE NOT LOCATED ON THE PLAN. VERIFY.
4. SHEET A2.1; KEYNOTES: NOTE 1 WAS NOT LOCATED ON THE PLAN. VERIFY.
5. SHEEET D-1; PARTITION C: ARE THE METAL STUDS CONNECTED AT THE MASONRY/CONCRETE WALL? VERIFY.
6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
09/04/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Clarify the scope of work for this activity, Dental Suite 100, as compared to activity T13CM05162 (Dental Suite 101).
09/05/2013 ROBERT SHERRY WATER REVIEW Approved
09/05/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Clarify the scope of work for this activity, Dental Suite 100, as compared to activity T13CM05162 (Dental Suite 101).
09/10/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM05163
10410 E Rita Ranch Road #100

1. Provide identification for curcuits on Sheet E1.0, note #29.

Ray T Majuta
Elect Plan Review
9/10/2013
Ray.majuta@tucsonaz.gov
520/837/4988