Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T13CM05162
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/01/2013 | MARTIN BROWN | FIRE | REVIEW | Approv-Cond | ONE SPRINKLER HEAD WILL BE REQUIRED IN MEDICAL GAS STORAGE ROOM. IT MAY BE SUPPLIED FROM THE DOMESTIC WATER. |
10/03/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
10/14/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Comment not addressed. [Initial comment: Special inspection of the medical gas installation by an inspector recognized by the City of Tucson is required. See http://cms3.tucsonaz.gov/files/dsd/Medical_Gas_Special_Inspection_Policy.pdf] |
10/14/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide the supporting documentation for required HVAC controls. [Initial comment: Complete the Mechanical Compliance Certificate by checking the appropriate line items in Section 4, the Requirements Checklist. Supporting documentation (e.g. for required HVAC controls) shall be either on the drawings or in the project manual.] 2. Clarify the area for which the heating and cooling loads apply; is the area covered by the existing A/C unit included in the calculations. [Initial comment: Provide the load calculations used to select AC-1 and AC-3. Verify that the output capacities do not exceed the calculated loads. Reference: Section C403.2, IECC 2012.] 3. Clarify how the size of the branch sprinkler pipe was sized; per Section 23.5.2.2.1, NFPA 13-2013, the minimum pipe size is 1" when using the pipe schedule method of adding sprinklers, [Initial comment: Verify that the door to the med gas storage room is a self-closing, smoke and draft-control assembly with a one-hour fire protection rating. Verify that the room is equipped with at least one automatic sprinkler. Reference: Section 502.9.1, IMC 2012 and Section 5306.2.1, IFC 2012.] |
10/15/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
10/22/2013 | SHANAE POWELL | OUT TO CUSTOMER | Completed |
10/22/2013 | CPIERCE1 | REJECT SHELF | Completed |