Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T13CM05162
Parcel: 14117015C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM05162
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/22/2013 MARTIN BROWN FIRE REVIEW Approv-Cond ONE SPRINKLER HEAD WILL BE REQUIRED IN MEDICAL GAS STORAGE ROOM. IT MAY BE SUPPLIED FROM THE DOMESTIC WATER.
08/29/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A0.0 (PROJECT INFORMATION); SHEET A1.0 (BUILDING INFORMATION); SHEET A1.0 (ALLOWABLE AREA): SHEET A0.0 AND SHEET A1.0 (BUILDING INFORMATION) LIST THE CONSTRUCTION TYPE AS VB, WHILE SHEET A1.0 (ALLOWABLE AREA) LISTS THE CONSTRUCTION TYPE AS IIB. CLARIFY.
2. SHEET A2.0 (FLOOR PLAN); FLOOR PLAN KEYNOTES: NEAR DOOR 118, THERE IS A KEYNOTE 30 INDICATED. IS THIS KEYNOTE LOCATION CORRECT? VERIFY.
3. SHEET A2.0; KEYNOTES: NOTES 11, 15, 31, AND 33 WERE NOT LOCATED ON THE PLAN. VERIFY.
4. SHEET A2.1; KEYNOTES: NOTE 1 WAS NOT LOCATED ON THE PLAN. VERIFY.
5. SHEEET D-1; PARTITION C: ARE THE METAL STUDS CONNECTED AT THE MASONRY/CONCRETE WALL? VERIFY.
6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
09/03/2013 ROBERT SHERRY WATER REVIEW Approved
09/04/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The specified "tankless water heater" is actually a special-purpose water heater with a small storage tank (2/3 gallon) and is designed to dispense near-boiling water. It is factory-set to dispense 200F water but can be adjusted from 160F to 210F. Tankless water heaters used for domestic uses (i.e. not process use) shall be limited to a maximum discharge temperature of 140F. Hand-washing sinks and lavatories shall be equipped with a listed temperature limiting device set for a maximum of 110F.Reference: Sections 416.5, 501.6 and 607.1.2, IPC 2012.
2. Clarify keynote 9 on sheet P1.0. It is not clear how the hose bibb relates to the reduced pressure backflow preventer, what is ultimately connected to the backflow preventer, and the location of the mop sink referenced in the keynote.
3. Special inspection of the medical gas installation by an inspector recognized by the City of Tucson is required. See http://cms3.tucsonaz.gov/files/dsd/Medical_Gas_Special_Inspection_Policy.pdf
09/04/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The Mechanical Compliance Certificate on sheet M1.1 states that the new packaged heat pumps will have a 14.5 SEER and, in addition, the high efficiency HVAC option has been selected for the new packaged heat pumps. Under that option, a minimum efficiency of 15 SEER is required for the units. The specified units, however, have an efficiency of only 13.5 SEER. Clarify how the addition of the new heat pumps will comply with the requirements of Section C406, IECC 2012.
2. Complete the Mechanical Compliance Certificate by checking the appropriate line items in Section 4, the Requirements Checklist. Supporting documentation (e.g. for required HVAC controls) shall be either on the drawings or in the project manual.
3. Provide the load calculations used to select AC-1 and AC-3. Verify that the output capacities do not exceed the calculated loads. Reference: Section C403.2, IECC 2012.
4. Clarify keynote 9 on sheet M1.0; it is used in room 118.
5. Verify that the door to the med gas storage room is a self-closing, smoke and draft-control assembly with a one-hour fire protection rating. Verify that the room is equipped with at least one automatic sprinkler. Reference: Section 502.9.1, IMC 2012 and Section 5306.2.1, IFC 2012.
09/06/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM05162
10410 E Rita Ranch RD 101
TI Dental

1. Sheet E1.0, Power Plan Keynotes:
#1 refers to Panel location, on plan #1 is the SES,
#2 refers to telephone bd, on plan it's a phone outlet
please review these so as to indicate correct item.
2. Medical Gas use, verify the if medical type gas to be used is of a flamable type or non flamable. If non flamable type
indicate on plan , if flamable type indicate "Installation to comply with 2011 NEC517.60 (A).
3. Circuits 40,42 used for inst wh's are just labeled in the middle of the utility room. Show disconnect for each one and actual location of installation. NEC 2011,422.31.
4. Provide circuit numbers for items 28,29,30 on Sheet E1.0.
5. Sheet E2.0, indicate which fixtures are fed from circuit 2 and which are fed from circuit 4. They appear to combine.
6. Sheet E2.0, issue circuit numbers to items10,11,12.
7. Sheet 3.0, indicate on plan if SES feeds only the 400 amp and 200 amp panels shown. If other panels are fed from this SES, provide a total load and describe how obtained.
8. Sheet E3.0, identify the fixtures listed in the IECC Interior Lighting Compliance Report with the ones shown in the Lighting Schedule on Sheet E2.0.

Ray T Majuta
Elect Plan Review
PDSD, Tucson
9/6/2013
Ray.majuta@tucsonaz.gov
520/837/4988
provide total load on SES from all panels fed.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/30/2013 AROMERO4 OUT TO CUSTOMER Completed
09/30/2013 CPIERCE1 REJECT SHELF Completed