Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM05162
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/22/2013 | MARTIN BROWN | FIRE | REVIEW | Approv-Cond | ONE SPRINKLER HEAD WILL BE REQUIRED IN MEDICAL GAS STORAGE ROOM. IT MAY BE SUPPLIED FROM THE DOMESTIC WATER. |
08/29/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A0.0 (PROJECT INFORMATION); SHEET A1.0 (BUILDING INFORMATION); SHEET A1.0 (ALLOWABLE AREA): SHEET A0.0 AND SHEET A1.0 (BUILDING INFORMATION) LIST THE CONSTRUCTION TYPE AS VB, WHILE SHEET A1.0 (ALLOWABLE AREA) LISTS THE CONSTRUCTION TYPE AS IIB. CLARIFY. 2. SHEET A2.0 (FLOOR PLAN); FLOOR PLAN KEYNOTES: NEAR DOOR 118, THERE IS A KEYNOTE 30 INDICATED. IS THIS KEYNOTE LOCATION CORRECT? VERIFY. 3. SHEET A2.0; KEYNOTES: NOTES 11, 15, 31, AND 33 WERE NOT LOCATED ON THE PLAN. VERIFY. 4. SHEET A2.1; KEYNOTES: NOTE 1 WAS NOT LOCATED ON THE PLAN. VERIFY. 5. SHEEET D-1; PARTITION C: ARE THE METAL STUDS CONNECTED AT THE MASONRY/CONCRETE WALL? VERIFY. 6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
09/03/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
09/04/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The specified "tankless water heater" is actually a special-purpose water heater with a small storage tank (2/3 gallon) and is designed to dispense near-boiling water. It is factory-set to dispense 200F water but can be adjusted from 160F to 210F. Tankless water heaters used for domestic uses (i.e. not process use) shall be limited to a maximum discharge temperature of 140F. Hand-washing sinks and lavatories shall be equipped with a listed temperature limiting device set for a maximum of 110F.Reference: Sections 416.5, 501.6 and 607.1.2, IPC 2012. 2. Clarify keynote 9 on sheet P1.0. It is not clear how the hose bibb relates to the reduced pressure backflow preventer, what is ultimately connected to the backflow preventer, and the location of the mop sink referenced in the keynote. 3. Special inspection of the medical gas installation by an inspector recognized by the City of Tucson is required. See http://cms3.tucsonaz.gov/files/dsd/Medical_Gas_Special_Inspection_Policy.pdf |
09/04/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. The Mechanical Compliance Certificate on sheet M1.1 states that the new packaged heat pumps will have a 14.5 SEER and, in addition, the high efficiency HVAC option has been selected for the new packaged heat pumps. Under that option, a minimum efficiency of 15 SEER is required for the units. The specified units, however, have an efficiency of only 13.5 SEER. Clarify how the addition of the new heat pumps will comply with the requirements of Section C406, IECC 2012. 2. Complete the Mechanical Compliance Certificate by checking the appropriate line items in Section 4, the Requirements Checklist. Supporting documentation (e.g. for required HVAC controls) shall be either on the drawings or in the project manual. 3. Provide the load calculations used to select AC-1 and AC-3. Verify that the output capacities do not exceed the calculated loads. Reference: Section C403.2, IECC 2012. 4. Clarify keynote 9 on sheet M1.0; it is used in room 118. 5. Verify that the door to the med gas storage room is a self-closing, smoke and draft-control assembly with a one-hour fire protection rating. Verify that the room is equipped with at least one automatic sprinkler. Reference: Section 502.9.1, IMC 2012 and Section 5306.2.1, IFC 2012. |
09/06/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T13CM05162 10410 E Rita Ranch RD 101 TI Dental 1. Sheet E1.0, Power Plan Keynotes: #1 refers to Panel location, on plan #1 is the SES, #2 refers to telephone bd, on plan it's a phone outlet please review these so as to indicate correct item. 2. Medical Gas use, verify the if medical type gas to be used is of a flamable type or non flamable. If non flamable type indicate on plan , if flamable type indicate "Installation to comply with 2011 NEC517.60 (A). 3. Circuits 40,42 used for inst wh's are just labeled in the middle of the utility room. Show disconnect for each one and actual location of installation. NEC 2011,422.31. 4. Provide circuit numbers for items 28,29,30 on Sheet E1.0. 5. Sheet E2.0, indicate which fixtures are fed from circuit 2 and which are fed from circuit 4. They appear to combine. 6. Sheet E2.0, issue circuit numbers to items10,11,12. 7. Sheet 3.0, indicate on plan if SES feeds only the 400 amp and 200 amp panels shown. If other panels are fed from this SES, provide a total load and describe how obtained. 8. Sheet E3.0, identify the fixtures listed in the IECC Interior Lighting Compliance Report with the ones shown in the Lighting Schedule on Sheet E2.0. Ray T Majuta Elect Plan Review PDSD, Tucson 9/6/2013 Ray.majuta@tucsonaz.gov 520/837/4988 provide total load on SES from all panels fed. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/30/2013 | AROMERO4 | OUT TO CUSTOMER | Completed |
09/30/2013 | CPIERCE1 | REJECT SHELF | Completed |