Permit Number: T13CM05156
Parcel: 12510003G

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T13CM05156
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/09/2013 MARTIN BROWN FIRE REVIEW Approved
10/10/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/14/2013 DAVID RIVERA ZONING REVIEW Reqs Change From: David Rivera, Principal Planner
PDSD Zoning Reviewer

Date: October 14, 2013

Project: T13CM05156
Building plan review for the Cheddar's Restaurant at El Con

Address: 3455 E Broadway Blvd.

(As of this second review the development package site plan has not been fully approved by all reviewing agencies including zoning.)

1. Zoning has reviewed the building plans for compliance with the Development Package in for review. While the building plans are in substantial compliance with the Preliminary development package site zoning cannot approve the buildings plans until the development package is approved.

2. Zoning will re-review the building plans on the next submittal and compare them to the approved Development Package. Keep in mind that the building plans cannot be approved by zoning until a full approval of the development package has occurred.

3. Zoning is willing to review the building plans over the counter on the next submittal with an appointment, assuming the development package site plan is approved and stamped and available or included with the building plan package. Call in advance for the appointment so I can reserve a time slot to go over the plans.
10/18/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/18/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
10/18/2013 LOREN MAKUS ENGINEERING REVIEW Approved
10/18/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not resolved, provide a sediment trap for each water heater. Reference: Section 408.4, IFGC 2012. [Second comment: The installation of the water heaters, as shown on sheet P1.3, shows a quick disconnect valve located after a shut off valve that serves both water heaters. Provide justification for the installation of a quick disconnect valve for this service. Each water heater shall have an individual shut off valve and a sediment trap. Reference: Sections 404.16 (exception), 408.4, and 409.5.1, IFGC 2012.] [Initial comment: Clarify the gas valves shown on the gas floor plan (P1.3). The water heaters and each kitchen appliance have both a shutoff cock and another valve that appears to be similar to your symbol for an electric solenoid valve. The additional valves are not shown on the gas isometric diagram (P2.3).]
2. Comment not resolved. No pipe sizing calculations were found. [Second comment: Comment not resolved; pipe sizing calculations beyond a listing of the water fixture units have not been submitted and many of the pipe sizes are missing or appear to be incorrect (e.g. 1" pipes serving the flush-valve water closets or a 1-1/4" pipe serving three lavatories, a urinal, and four flush-valve water closets for a total demand of 50 GPM)] [Initial comment: Provide calculations showing how the water supply piping has been sized. Show all of the pipe sizes on the drawings (i.e. on the plumbing plan or the water supply isometric diagram). Reference: Sections 604.1 and 604.3, IPC 2012.]
3. Comment not resolved. Backflow protection for the hood was not called out. (Keynote #22 on sheet P1.1 alluded to the drain for a reduced pressure backflow assembly but no item #22 was on the drawing.) [Second comment: Show how backflow protection is to be provided for the hood.] [Initial comment: Provide backflow protection for the pollution control unit (PCU-1). Reference: Sections 608.16.6 and 608.16.7, IPC 2012.]

Final Status

Task End Date Reviewer's Name Type of Review Description
11/07/2013 FERNE RODRIGUEZ OUT TO CUSTOMER Completed
11/07/2013 CPIERCE1 REJECT SHELF Completed