Permit Number: T13CM05087
Parcel: 12708187F

Review Status: Completed

Review Details: OTHER

Permit Number - T13CM05087
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/17/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The natural gas utility, Southwest Gas, will provide gas service at 7" WC, 2 PSIG, and 5 PSIG. Service at ½ PSIG (13.9" WC) is not available. Revise the size of the gas piping as required. Reference: Section 402.3, IFGC 2012. [Second comment: The submitted information does not include a natural gas load for RTU-4 (existing), any other loads that may be served by the same gas meter, the pipe sizes upstream of the branch serving RTU-4, or if the piping is fed with a pressure greater than 8" WC. If the natural gas system is not operating at a medium pressure (e.g. 2 PSIG), provide the calculations used to determine that the system was properly sized.] [Initial comment: Verify that the existing gas piping is adequate to serve the new gas-fired rooftop units. Show the gas piping serving the proposed gas-fired units, including the pipe sizes and the developed pipe length to each of the units. Reference: Section 402.1, IFGC 2012.]
11/12/2013 FRODRIG2 MECHANICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/12/2013 FERNE RODRIGUEZ OUT TO CUSTOMER Completed