Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T13CM05087
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/17/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The natural gas utility, Southwest Gas, will provide gas service at 7" WC, 2 PSIG, and 5 PSIG. Service at ½ PSIG (13.9" WC) is not available. Revise the size of the gas piping as required. Reference: Section 402.3, IFGC 2012. [Second comment: The submitted information does not include a natural gas load for RTU-4 (existing), any other loads that may be served by the same gas meter, the pipe sizes upstream of the branch serving RTU-4, or if the piping is fed with a pressure greater than 8" WC. If the natural gas system is not operating at a medium pressure (e.g. 2 PSIG), provide the calculations used to determine that the system was properly sized.] [Initial comment: Verify that the existing gas piping is adequate to serve the new gas-fired rooftop units. Show the gas piping serving the proposed gas-fired units, including the pipe sizes and the developed pipe length to each of the units. Reference: Section 402.1, IFGC 2012.] |
| 11/12/2013 | FRODRIG2 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/12/2013 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |