Permit Number: T13CM05087
Parcel: 12708187F

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM05087
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/12/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/12/2013 MARTIN BROWN FIRE REVIEW Approved
09/23/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The submitted information does not include a natural gas load for RTU-4 (existing), any other loads that may be served by the same gas meter, the pipe sizes upstream of the branch serving RTU-4, or if the piping is fed with a pressure greater than 8" WC. If the natural gas system is not operating at a medium pressure (e.g. 2 PSIG), provide the calculations used to determine that the system was properly sized. [Initial comment: Verify that the existing gas piping is adequate to serve the new gas-fired rooftop units. Show the gas piping serving the proposed gas-fired units, including the pipe sizes and the developed pipe length to each of the units. Reference: Section 402.1, IFGC 2012.]
09/23/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not addressed. Complete the Mechanical Compliance Certificate by checking the appropriate line items in Section 4, the Requirements Checklist. Supporting documentation shall be either on the drawings or in the project manual.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/25/2013 CPIERCE1 REJECT SHELF Completed