Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM05087
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/12/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/12/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 09/23/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The submitted information does not include a natural gas load for RTU-4 (existing), any other loads that may be served by the same gas meter, the pipe sizes upstream of the branch serving RTU-4, or if the piping is fed with a pressure greater than 8" WC. If the natural gas system is not operating at a medium pressure (e.g. 2 PSIG), provide the calculations used to determine that the system was properly sized. [Initial comment: Verify that the existing gas piping is adequate to serve the new gas-fired rooftop units. Show the gas piping serving the proposed gas-fired units, including the pipe sizes and the developed pipe length to each of the units. Reference: Section 402.1, IFGC 2012.] |
| 09/23/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not addressed. Complete the Mechanical Compliance Certificate by checking the appropriate line items in Section 4, the Requirements Checklist. Supporting documentation shall be either on the drawings or in the project manual. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/25/2013 | CPIERCE1 | REJECT SHELF | Completed |