Permit Number: T13CM05087
Parcel: 12708187F

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM05087
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/19/2013 STEVE SHIELDS ZONING REVIEW Approved
08/19/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Complete the Mechanical Compliance Certificate by checking the appropriate line items in Section 4, the Requirements Checklist. Supporting documentation shall be either on the drawings or in the project manual.
2. Show the size, routing, and termination of the condensate drains. Reference: Sections 307.2.1, IMC 2012 as amended by the City of Tucson.
3. Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restrooms will be exhausted (i.e. the exhaust fan shall run whenever air is being supplied to the restrooms). The exhausted air from the restrooms shall be limited to no more than 10% of any subsequent supply air stream. Reference: Section 403.2.1 (4), IMC 2012.
08/19/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved LEERAY DID REVIEW AND APPROVAL
08/19/2013 ROBERT SHERRY WATER REVIEW Approved
08/19/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET CS1.1; SHELVING UNITS: REQUIREMENTS FOR SHELVING UNITS ARE: UP TO 6 FEET IN HEIGHT, NO EXTRA REQUIREMENTS FROM NOTE 1. OVER 6 FEET AND UP TO 12 FEET IN HEIGHT, SHOW DETAILS ON THE DRAWINGS OF THE SHELVING BRACING AND THE CONNECTION OF THE SHELVES TO THE FLOOR (SIZE AND QUANTITY). OVER 12 FEET IN HEIGHT, STRUCTURAL CALCULATIONS AND DETAILS ON THE DRAWINGS ARE REQUIRED FOR THE SHELVING BRACING AND CONNECTIONS TO THE FLOOR (SIZE AND QUANTITY).
2. SHEET A1; ELEVATION A: PROVIDE THE DIMENSION OF THE HEIGHT OF THE HORIZONTAL GRAB BAR ABOVE THE FLOOR.
3. GENERAL: INTERIOR PARTITIONS ARE REQUIRED TO RESIST A 5 PSF LATERAL LOAD PER THE IBC SECTION 1607.14. PROVIDE DETAILS FOR THAT BRACING, INCLUDING THE BRACING SIZE AND SPACING, AND THE CONNECTION (SIZE AND QUANTITY) OF THE BRACING TO THE TOP OF THE WALL AND TO THE STRUCTURE ABOVE.
4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
08/19/2013 LOREN MAKUS ENGINEERING REVIEW Approved
08/19/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Verify that the existing gas piping is adequate to serve the new gas-fired rooftop units. Show the gas piping serving the proposed gas-fired units, including the pipe sizes and the developed pipe length to each of the units. Reference: Section 402.1, IFGC 2012.
2. Zurn, the manufacturer of the specified temperature mixing valve, limits the use of the valve to a single outlet, not multiple outlets. Reference: Sections 303.2 and 416.5, IPC 2012.
3. Provide structural calculations for the mounting shelf for the water heater to show that the water heater will be safely supported from the building structure. Reference: Section 301.2, IPC 2012.
08/19/2013 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/20/2013 SPOWELL1 WWM REVIEW Needs Review
08/20/2013 MARTIN BROWN FIRE REVIEW Denied Fire sprinkler system must be monitored by a listed central station. Verify alarm panel is listed for fire protection. Add note indicating a fire department approved lock box exists or will be provided.
08/20/2013 MARTIN BROWN FIRE REVIEW Denied remove comment regarding alarm panel since it is a deferred submittal