Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/15/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
08/15/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
08/15/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
08/15/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
08/15/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
08/15/2013 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
08/15/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The new 3" horizontal drain is shown connecting to an existing 4" building drain. Does the 4" building drain have an existing cleanout located upstream of the new connection or is the connection at the upstream terminal of the 4" building drain. 2. Indirect waste piping that has a developed length greater than 30-inches (30") when measured horizontally or greater than 54-inches (54") in total developed length shall be trapped. Exception: indirect waste piping conveying only clear-water waste (e.g. effluent from a sanitizing compartment) does not require a trap. Reference: Section 802.2, IPC 2012. |
08/15/2013 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
08/16/2013 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
08/21/2013 | GERRY KOZIOL | WWM | REVIEW | Approved |