Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T13CM04997
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/09/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Reqs Change | The documents submitted for this building permit in no way what so ever reflect the existing deterorated conditions of the structures and solutions for repair. As per the 2012 IBC, Section 105.3 and 107, a complete set of construction documents describing all conditions for repair of the existing structures is to be developed by an engineer or architect registered in the State of Arizona. All documents are to be sealed and signed by the registrant. All structural repairs are to be structurally detailed and accomplied by a set of structural calculations also signed and sealed by the registrant. END OF REVIEW |
| 09/09/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Provide complete plumbing plans for the new work, including gas piping, water isometrics and waste and vent isometrics, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304 and Section 107.2.1, IBC 2012. |
| 09/09/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide complete mechanical plans for the new work, sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304 and Section 107.2.1, IBC 2012. |
| 09/09/2013 | ROBERT SHERRY | WATER | REVIEW | Denied | Show the location of the existing water and the required reduced pressure backflow preventer serving the buildings. Reduced pressure backflow prevention assemblies are required at the water meter for apartment buildings that have common laundry facilities that are served by the same meter that serves the building. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://cms3.tucsonaz.gov/sites/default/files/water/docs/backflow-ordinance.pdf |
| 09/09/2013 | KEN BROUILLETTE | FIRE | REVIEW | Reqs Change | PLEASE PROVIDE A CODE REVIEW OF THIS PROJECT. I HAVE NO IDEA WHAT THE OCCUPANCY CLASSIFICATION, TYPE OF CONSTRUCTION OR WHICH CODE THIS PROJECT IS BEING SUBMITTED. |
| 09/10/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | C of Tuc Requirements: Provide a Panel Schedule inclusive of loads - 1 is ok if all unit identical circuits. Ray T. Majuta Elec Plan Reviewer 520-837-4988 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/11/2013 | CPIERCE1 | REJECT SHELF | Completed |