Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T13CM04983
Parcel: 12315102B

Address:
701 E ADAMS ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU

Permit Number - T13CM04983
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/17/2013 LHANLY1 ZONING REVIEW Reqs Change See comments from Steve Shields in previous review.
09/17/2013 LEE HANLY BUILDING-RESIDENTIAL REVIEW Reqs Change There is minor erratta throughout plans concerning structural, plumbing, & mechanical systems, etc. This errata will be discussed with applicant in person for correction. Following corrections are in addition to the errata.

1) Provide information for the thermal envelope of the building

2) Provide Manual J calculations for mechanical systems

3) Show connections of dishwasher to water supply and waste.

4) Tucson Water limits a 5/8" meter to a max demand of 15GPM, and a 3/4" meter to 22.5 GPM. Your total demand is 20 GPM for condo's 2-6 and will be higher than that for condo 1 when irrigation is connected.

5) Provide scupper sizing calculation for roof area and indicate secondary (overflow) drainage. Sizing calculations to be given for required downspout also.

6) indicate location of carbon monoxide detectors.