Permit Number: T13CM04959
Parcel: 99999999M

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T13CM04959
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/14/2013 MARTIN BROWN FIRE REVIEW Approved
08/19/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
08/19/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
08/19/2013 ROBERT SHERRY WATER REVIEW Passed
08/23/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET 7; WATER ASSEMBLY PROFILE D: THE NOTE FOR THE CONCRETE SLAB REINFORCING INDICATES "11 #4 BARS @ 16' SPACING.....". REVISE THE SPACING TO 16".
2. SHEET 9; SECTION 3: PROVIDE A NOTE INDICATING THE REINFORCING IN THE SLAB, OR REFERENCE ANOTHER SECTION/PLAN FOR THAT REINFORCING.
3. SHEET 11; SHEET 13: IS THERE A REASON GENERAL STRUCTURAL NOTES ARE SHOWN ON BOTH SHEETS? VERIFY. COULD THESE BE COMBINED TO INCLUDE NOTES FOR THE SITE WALLS AND THE SHADE STRUCTURE?
4. SHEET 12; FOUNDATION PLAN: ADD A NOTE TO THE 17' DIMENSION ON THE NORTH END OF THIS PLAN THAT THE DIMENSION IS TO THE CENTERLINE OF THE PIER AND BRACE BEYOND.
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
08/28/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/29/2013 CPIERCE1 REJECT SHELF Completed