Review Status: Completed
Review Details: COMMERCIAL - NEW
Permit Number - T13CM04959
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/14/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
08/19/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
08/19/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
08/19/2013 | ROBERT SHERRY | WATER | REVIEW | Passed | |
08/23/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET 7; WATER ASSEMBLY PROFILE D: THE NOTE FOR THE CONCRETE SLAB REINFORCING INDICATES "11 #4 BARS @ 16' SPACING.....". REVISE THE SPACING TO 16". 2. SHEET 9; SECTION 3: PROVIDE A NOTE INDICATING THE REINFORCING IN THE SLAB, OR REFERENCE ANOTHER SECTION/PLAN FOR THAT REINFORCING. 3. SHEET 11; SHEET 13: IS THERE A REASON GENERAL STRUCTURAL NOTES ARE SHOWN ON BOTH SHEETS? VERIFY. COULD THESE BE COMBINED TO INCLUDE NOTES FOR THE SITE WALLS AND THE SHADE STRUCTURE? 4. SHEET 12; FOUNDATION PLAN: ADD A NOTE TO THE 17' DIMENSION ON THE NORTH END OF THIS PLAN THAT THE DIMENSION IS TO THE CENTERLINE OF THE PIER AND BRACE BEYOND. 5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
08/28/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
08/29/2013 | CPIERCE1 | REJECT SHELF | Completed |