Permit Number: T13CM04858
Parcel: 11710019A

Address:
361 N MEYER AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU

Permit Number - T13CM04858
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/02/2014 RAFAEL CANCINO BUILDING-RESIDENTIAL REVIEW Needs Review
08/15/2013 LOREN MAKUS ENGINEERING REVIEW Approved
08/27/2013 STEVE SHIELDS ZONING REVIEW Approved CDRC TRANSMITTAL


FROM: Steve Shields, Lead Planner

PROJECT: T13CM04858
361 North Meyer Avenue
Addition to existing SFR


TRANSMITTAL: August 27, 2013


COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.


This site is in the HO-3 Zone. Historic review is required (UDC Sections 3.3.7 and 5.8.5). (This project is scheduled for historic review.)

A single-family residence is a permitted use in this zone (UDC Section 4.7.15).

The historic review is required for building addition.

Per UDC Table 6.3-3.A Residential Use to Non-Residential Zone the required perimeter yard setback is 10 or ¾ the height of the building exterior wall. Based on a wall height of 19'-4' the required perimeter yard setback to the north property line is 14'-6", proposed perimeter yard setback is 0'-0".
08/27/2013 SSHIELD1 NPPO REVIEW Passed